Product Details:
|
|
Place of Origin: | China |
---|---|
Brand Name: | HAISEN |
Certification: | UL BC |
Model Number: | ES-EIA-01S SERIES |
Payment & Shipping Terms:
|
|
Minimum Order Quantity: | 100pcs |
Price: | Negotiable |
Packaging Details: | Packed in Bubble Bag, Reinforced With Paper Flat, Then Packed With Outer Carton |
Delivery Time: | Standard Models Within 3 Weeks |
Payment Terms: | D/A, D/P, T/T |
Supply Ability: | 1-10pcs Samples Within 2-3 Days; Bulk Order Within 28 Days |
Description
Features
-Battery overcharge protection
-Battery over-discharge protection
-Output overload protection
-Short-circuit protection
-Open load protection
ELECTRICAL SPECIFICATIONS
Input voltage | 100-347 VAC 50/60Hz |
Input Current | 0.1A max |
Input Power | 8W Max |
Power Factor | 0.6@100VAC,0.5@347VAC |
Input of LED load | AC 6A Max |
Output Voltage | 140Vdc |
Battery | Lithium |
Recharge duration | <24Hrs |
Emergency duration | 90mins |
Ambient temp | 0-50°C(32℉-122℉) |
MODEL SELECTION TABLE
Models |
ES-EIA09-01S
|
ES-EIA15-01S
|
ES-EIA25-01S | ES-EIA25-01S | ES-EIA25-01S |
Emergency wattage |
9W
|
15W
|
25W | 32W | 38W |
Battery capacity
|
14.8V/1800mAh
|
14.8V/600mAh
|
14.8V/4400mAh
|
14.8V/5200mAh
|
14.8V/6600mAh
|
Compatible led fixture
|
9-80W LED lamp with
0-10V dimming or
LED lamp less than 9W
without 0-10V dimming
|
15-120W LED lamp with
0-10V dimming or
LED lamp less than 15W
without 0-10V dimming
|
25-200W LED lamp with
0-10V dimming or
LED lamp less than 25W
without 0-10V dimming
|
32-300W LED lamp with
0-10V dimming or
LED lamp less than 32W
without 0-10V dimming
|
38-350W LED lamp with
0-10V dimming or
LED lamp less than 38W
without 0-10V dimming
|
DIMENSION
Model | L |
W
|
H |
ES-EIA09-01S
|
14.6"(371mm)
|
1.62"(41.4mm)
|
1.43"(36.4mm)
|
ES-EIA15-01S
|
14.6"(371mm)
|
1.62"(41.4mm)
|
1.43"(36.4mm)
|
Model |
L
|
W | H |
ES-EIA25-01S
|
2.24"(311mm)
|
2.59"(66mm)
|
1.53"(39mm)
|
ES-EIA32-01S
|
12.24"(311mm)
|
2.59"(66mm)
|
1.53"(39mm)
|
ES-EIA38-01S
|
12.24"(311mm)
|
2.59"(66mm)
|
1.53"(39mm)
|
EMERGENCY MODE
1.The emergency battery backup enters the emergency mode immediately after the mains power failure.
2.Stop the emergency and return to the charging state after the mains power call.
SELF-TEST