Send Message

Led Fixtures Ul List Emergency Converter , Lithium External Led Driver

Product Details:
Place of Origin: China
Brand Name: HAISEN
Certification: UL BC
Model Number: ES-EOC08-HV
Payment & Shipping Terms:
Minimum Order Quantity: 100pcs
Price: Negotiable
Packaging Details: Packed in Bubble Bag, Reinforced With Paper Flat, Then Packed With Outer Carton
Delivery Time: Standard Models Within 3 Weeks
Payment Terms: D/A, D/P, T/T
Supply Ability: 1-10pcs Samples Within 2-3 Days; Bulk Order Within 28 Days
Specifications Product Description Request A Quote
Specifications
Specifications
Features: 2-in-1 LED Test Switch And Indicator Light Included
Color: Light Yellow
Products: LED Emergency Driver
Battery: Lithium
Input Voltage: 100-347VAC,50/60Hz
Warranty: 5 Years Limited
High Light:

Ul List Emergency Converter

,

Lithium External Led Driver

,

60Hz UL Version Emergency LED Driver

Product Description

Ul List Emergency Converter Suit For Led Fixtures With Eaternal Led Driver

Description

  • 1:ES-EOC series suit for LED fixtures with external LED driver;
  • 2:The output current of the LED driver can not exceed 5A to work with ES-EOC08-02S-LV family;the output current of the LED driver can not exceed 1.5A to work with ES-EOC08-02S-HV family

Features

  • UL listed for field or factory installation, CEC title 20 compliant
  • Compliance with American NFPA 101 life Safety Code
  • Constant output power
  • 2-in-1 LED test switch and indicator light included
  • Manual testing via remote control(optional)
  • Monthly/annual self-testing
  • With multi-protection function:

​         -Battery overcharge protection
         -Battery over-discharge protection
         -Output overload protection
         -Short-circuit protection

         -Open load protection

  • 5 years limited warranty

 
ELECTRICAL SPECIFICATIONS

Input voltage 100-347 VAC 50/60Hz
Input Current 0.08A max
Input Power 5W Max
Power Factor 0.5@220VAC
Output Voltage  90-300Vdc
Battery
LiFePO4 6.4V 3200mAh
Recharge duration <24Hrs
Emergency duration 90mins
Ambient temp 0-50°C(32℉-122℉)

 

 

MODEL SELECTION TABLE

Models

 

ES-EOC08-02S-LV-S

 

ES-EOC08-02S-LV-L

 

ES-EOC08-02S-HV-S
ES-EOC08-02S-HV-L
Output voltage

 

20-60V

 

 

20-60V

 

90-300V
90-300V

 

 

 

 

DIMENSION

Led Fixtures Ul List Emergency Converter , Lithium External Led Driver 0

 

 

 

NORMAL MODE
Fixtures will operate normally when power is available. When an outage occurs, the fixture will switch to emergency mode, delivering power to the fixture for up to 90 minutes.

 

EMERGENCY MODE

1. The emergency battery backup enters the emergency mode immediately after the mains power failure.

2. Stop the emergency and return to the charging state after the mains power call.


SELF-TEST

MONTHLY SELF-TEST
It will automatically perform a monthly self-test every 30 days with a duration of 30S to check whether the emergency function is normal, and automatically restore to normal charging after 30S discharged.
 
ANNUAL SELF-TEST
An annual self-test will be done every year(12 months) with a duration of more than 180mins to check whether the capacity of the battery pack is normal, and automatically restore to normal charging after fully discharged. (the condition of annual test is that the battery pack is fully charged). If the annual inspection is interrupted, it will be retested after recovery and when the test conditions are met. (Possibility of interruption: such as sudden power failure, sudden manual test).
 
 

Led Fixtures Ul List Emergency Converter , Lithium External Led Driver 1

 

ES-EOC 2-4-8W.pdf

 

 

 

Get in touch with us
Contact Person : Miss. Evelyn Chow
Tel : 13410390591